Product Center

Product Center

PHF-DL-L Series Dynamic Balancing Valve (Thread Type)

PHF-DD-L

Model Selection Description

Order No. Model No. DN Thread  GA Thread  GB øA PN Flow m3/h(under 0.1~0.35MPa pressure)
14074 PHF-DL-20L DN20 G3/4 G3/4 31 PN16 1.1
14075 PHF-DL-25L DN25 G1 G1 42.5 PN16 1.1



Structure Principle

The application of dynamic flow balance valve is mainly in the initial adjustment of the system such as the initial distribution of central air conditioning,water and heating supply.It consists of a valve shell and a valve core.The valve core is the hydraulic automatic regulating orifice plate.And the hydraulic automatic regulating orifice plate is composed of  a valve liner which  can be automatically adjusted by the flow area and a high precision spring.Spring can automatic control the size of the flow area on the gall of the valve based on both ends of the differential pressure automatic control valve to maintain a constant flow of water.
● The differential pressure between the front and back of the balancing valve is less than minimum starting differential pressure.
     In this case, the spring will not be compressed (the gall of the valve has a preload when assemble), the valve is in a static state, the  flow area is the largest.And the water flow through the balancing valve increases with the increase of differential pressure at this time 
● The differential pressure between the front and back of the balancing valve is within the working range of the calibration
     At this time,the top of the gall of the valve under the action of fluid pressure begins to compress spring, the balancing valve gets into the working state. In the working pressure range, if the fluid pressure changes,  the curve of excess channel on the gall of the valve will change accordingly.So in this pressure range, no matter how the pressure changes, output end of the water flow will be maintained.
● The differential pressure between the front and back of the balancing valve above the operating range:
     In this state,the spring in the inner of the balancing valve will be completely compressed. The water can only flow through a circular hole on both sides of the gall.The flow area will be maintained, and the flow is proportional to the differential pressure, and increases with the increase of the differential pressure.


 

Installation instructions

 


        This product can be applied to any kinds of motorised valve and ball valve. Make sure that the valves' moving direction is the same as the dynamic balancing valves' arrow. The installation is very easy. You just need to screw up the product and the valve.